Grupos estáticos monofásicos con disipador, con mando lógico – W211

Fin de producción

Grupos estáticos monofásicos con disipador, con mando lógico – W211

Fin de producción

Características principales
  • Conduction inhibition input
  • Overcurrent protection (DE option)
  • Detection of partial load failure (RPC option)
Producto sustitutivo
GPC
Controlador de potencia avanzado mono/bi/trifásico hasta 600A

Datos técnicos

Panorámica

Wattcor W211 line offers a wide range of solid state power controllers with "zero crossing" switching for resistive loads with current ratings up to 600A and 660Vac nominal voltages.
The models of the W211 series accept Vdc and Vac logic controls. The conduction is activated by the control signal at the first zero crossing of the load power voltage. Switching off occurs by the first zero crossing of the load current after disabling the control signal.
The control of three-phase loads can be by two or three W211 in series and fired in parallel. Each model is equipped with a logic input to disable the solid state relay/power controller and eventually break off power supply.
Different options are available for the more critical applications, such as the "load control" (RPC option) which detects and indicates partial load failure interruption/cut-off, with a LED on the faceplate, and a relay alarm output. The DTC option allows the control of a possible SCR short-circuit or the complete current failure in the load.
A further safety option is represented by the "electronic cut-off" circuit, (DE option), a device protecting the power element against a momentary excess current higher than a selected value, corresponding to approx. 13 times the nominal current of the solid state power controller. The alarm condition disables the power supply, activates an alarm relay (in common with RPC option) and allows the instrument resetting through a front button.
The WATTCOR W211 series are designed to guarantee nominal current and voltage values at 50°C ambient temperature, with a working temperature range from -5°C up to 60°C. 250A and 600A units are supplied with internal fuse and digital output for the fuse status. Signal connections are made via "plug-in" connectors to enable easy wiring.
The instrument can be DIN rail or panel mounted (from 250 up to 600A current ratings, panel mounting only).

Zero-voltage switching. Current range: 25A to 600A, diagnostics and load interrupt alarm

  • Conduction inhibition input
  • Overcurrent protection (DE option)
  • Detection of partial load failure (RPC option)
  • SCR diagnosis circuit and complete load failure (DTC option)
  • Input control from Vdc and Vac logic signal
  • Zero crossing switching of mains voltage
  • High capacity anti-parallel SCR double thyristor
  • LED status indicators
  • MOV protections (varistor)
  • DIN rail or panel mounting (depending on version)